I8-M120 incinerator is specially designed for medical waste. This model is a controlled air incinerator, providing optimal combustion conditions for different waste types. The top loading design provides liquid retention making this incinerator ideal for incineration of many different waste types. This unit benefits from a secondary chamber with afterburner for the re-burn of harmful emissions with a 2 second retention time.
Emission Data
Average emissions / EU standards On basic incinerators (with secondary chamber)
Parameter |
Limits
(1/2 hr av) |
Measured |
Total dust |
30 mg/m3 |
12 mg/m3 |
Sulphur dioxide |
200 mg/m3 |
2,4 mg/m3 |
Nitrogen dioxide* |
400 mg/m3 |
60 mg/m3 |
Carbon monoxide |
100 mg/m3 |
78,3 mg/m3 |
Typical Medical Waste Applications
Technical Specs
Operational Specs |
Physical Specs |
Combustion Chamber Volume (m3) |
1.25m3 |
External Length (mm) |
1680mm |
Burn Rate* |
up to 100kg per hour
|
External Width (mm) |
960mm |
Average Fuel Consumption |
18 kg per hour |
External Height (mm) |
8000mm |
Operational Temperature |
850 - 1320°C |
Shipping Weight |
5000kg |
Gas Retention in Secondary Chamber |
2 secs |
|
|
Temperature Monitoring |
Yes |
|
|
Average ash residue (%) |
3% |
|
|
Thermostatic Device |
Yes |
|
|
*Subject to calorific value of waste stream. For reference only, not to be used for installation purposes.